1-805-484-2992

Quotes - Engineering - Sales

Replacing an Existing Refrigerated Air Dryer

Previous-generation models and the units that replace them

Request a quote

Replacing an Existing Refrigerated Air Dryer

Five of the series on this site are the previous generation: the HPR, HPRN, FLEX, HITN and HPET Series. Each still has its own page and part numbers, so an old unit can be identified, and each has a current successor that carries the same flows with a newer refrigerant, a lighter cabinet and in some sizes a different pipe connection. Replacing one is a matter of reading the nameplate, naming the successor, and checking three things that may have changed since the original was bought.

Where the old dryer is another make entirely, the same method applies through its rated flow; the cross-reference page covers that case.

Reading the old nameplate

The model number carries the series and usually the flow: HPRN250-4 is a 250 SCFM non-cycling unit on 460 V, FLX4.5 a 450 SCFM cycling unit, HITN50 a 50 SCFM high inlet temperature unit, HPET-1.0 a 300 SCFM high-pressure unit whose number is its refrigeration horsepower. Beside it are the rated flow and its conditions, which for these series are the same 100 psig, 100°F and 100°F point used across this site, then the maximum working pressure, the voltage and phase, the refrigerant, and the serial number, which dates the unit.

The connection size is on the drawing rather than the plate, and it is the item most often missed: the successor may be one pipe size different, and reducers are easier to order with the dryer than to find on the day it arrives.

The retired series

The successors, size for size

The HPR Series small cabinet dryers are replaced by the HPRB Series at the same flows, 7 to 50 SCFM. The FLEX Series is replaced by the FLXA Series under the same model numbering, so an FLX4.5 becomes an FLXA4.5-A. The HITN Series is replaced by the HRHT Series, rated for 200°F rather than 180°F inlet air, with the HTR Series covering the 125 SCFM size. The HPET Series is replaced by the HHPR Series at 680 psig, with the APET Series covering 725 psig duties and the smallest sizes.

The HPRN Series has no single successor. Its 75 to 1,200 SCFM range is covered flow for flow by the non-cycling DXR Series, which is the like-for-like replacement, or by the FLXA Series where the plant now runs the hours that make a cycling dryer pay.

The current series

Successor seriesnoun

The current line that takes over a retired series' flows, sometimes with a different refrigerant, cabinet or pipe connection, and is ordered in its place.

HPRB Series refrigerated air dryer close-up

Worked example: replacing an HPRN250-4

Same flow, one pipe size smaller

  • Old unit: 250 SCFM non-cycling, 2 in NPT, 460/3/60, 30 x 17 x 36 in, 205 lb
  • Plant unchanged: 50 hp screw in a ventilated room, one shift
  • Like for like: DXR 0250 NA, 250 SCFM, 1-1/2 in FNPT, 460/3/60, 36 x 23 x 24 in, 185 lb, with two 2 in to 1-1/2 in reducers
  • Had the plant added a second shift: FLXA3.1-A, 300 SCFM cycling, 2 in NPT, no reducers
FLXA Series refrigerated air dryer close-up

Reading the nameplate

Six lines that identify the replacement

  • Model number: series and, on most lines, the rated SCFM
  • Rated flow and rating conditions; maximum working pressure
  • Voltage, phase and frequency; refrigerant type
  • Serial number for the age, and the connection size from the drawing

Retired series and their successors

Flow for flow, with the changes to watch for when the new unit is piped in.

RETIRED SERIES SUCCESSOR WHAT CHANGES EXAMPLE
HPR, 5 to 50 SCFM HPRB, 7 to 50 SCFM 3/8 in tube and 3/4 in NPT become 3/8 in MNPT and 1/2 in FNPT; R513A; lighter cabinet HPR25 to HPRB25-A
HPRN, 75 to 1,200 SCFM DXR, non-cycling, or FLXA, cycling Pipe size differs by one step on several models; 4 in flanges become 3 in MNPT on 1,000 and 1,200 SCFM HPRN250-4 to DXR 0250 NA
FLEX, 75 to 2,000 SCFM FLXA, same model numbers with -A or -W Same connections through 1,250 SCFM; 1,500 and 2,000 SCFM move from 4 in to 6 in flanges FLX4.5 to FLXA4.5-A
HITN, 20 to 125 SCFM at 180°F HRHT, 25 to 100 SCFM at 200°F; HTR at 125 SCFM 3/4 in and 1 in NPT become 3/4 in MNPT or FNPT and 1 in FNPT; zero-loss drain fitted HITN50 to HRHT60A
HPET, 30 to 3,000 SCFM at 725 psig HHPR, 115 to 2,410 SCFM at 680 psig; APET, 45 to 1,000 SCFM at 725 psig Confirm the system pressure against 680 psig; Class 300 flanges from 750 SCFM on the HHPR HPET-0.5 to HHPR-200 or APET-200
1

Read the nameplate

Model, rated flow, voltage, refrigerant and serial number

2

Name the successor

Use the retired-series table to find the current model

3

Check what changed

Compressor, room temperature and shift hours

4

Order the reducers

With the dryer, if the pipe size is one step different

Successors to the retired series

HPRB Series refrigerated air dryer, three-quarter view

HPRB Series:

Non-Cycling

  • 7 to 50 SCFM
  • Non-Cycling
  • 200 psig max inlet
FLXA Series refrigerated air dryer, three-quarter view

FLXA Series:

Cycling

  • 75 to 2,000 SCFM
  • Cycling
  • 120°F max inlet
HRHT Series refrigerated air dryer, three-quarter view

HRHT Series:

High Inlet Temperature

  • 25 to 100 SCFM
  • High Inlet Temperature
  • 200°F max inlet

Three things to check before ordering

First, the compressor: if it has been replaced or a second one added, the delivered flow is not what the old dryer was sized for. Second, the room: a compressor room that has gained a machine since the dryer went in is hotter, and the ambient factor moves the sizing. Third, the hours: a plant that has grown from one shift to two has become a cycling duty. If all three are unchanged, the successor at the same rated flow is the order. If any has changed, size again on the sizing pages and treat the old rating as the floor.

Connections and footprint

Small cabinet dryers moved from 3/8 in tube and 3/4 in NPT on the HPR Series to 3/8 in MNPT and 1/2 in FNPT on the HPRB Series. The HPRN to DXR cross changes the pipe size on several models, up or down by one step, and swaps the 4 in flanges of the HPRN1000 and HPRN1200 for 3 in MNPT on the DXR 1050 and 1250. The FLXA 1,500 and 2,000 SCFM sizes moved from 4 in to 6 in flanges and stand taller than the FLEX units they replace.

Mistakes in replacement

Ordering the old rated flow when the plant has grown. Ordering a high-pressure HHPR unit for a 725 psig system its 680 psig rating does not cover, when the APET Series does. Matching an HITN at 180°F when the compressor's aftercooler has since failed and the air arrives hotter still. Assuming the successor's pipe size is the same. And replacing a dryer that was undersized from the start with one exactly as undersized, because it was the same number.

Refrigerants, voltage and power

The current series use R513A, R454C, R410A or R404A in place of the R-134a and R-407C of the retired lines; none of it affects the installation, since the circuits are sealed and charged. Voltages match size for size: 115 V single-phase on the small cabinets, 460 V three-phase from about 200 SCFM, with 230 V single-phase on several mid sizes. Power draw is generally equal or lower, and on a cycling replacement it falls with the load.

Swapping a retired dryer for its successor

It has to be recovered by a certified technician before the unit goes for disposal, since venting refrigerant is prohibited under the EPA Section 608 rules in the US. Most scrap yards want evidence that the circuit has been emptied before they will take the cabinet. Once the charge is out, the copper, aluminum and steel in the old dryer are ordinary scrap metal.

Decide on the hours, not on the old nameplate. On one shift with the compressor off overnight, the like-for-like non-cycling unit is the cheaper purchase and a cycling dryer saves little power. On two or three shifts, or where the dryer runs at part load for long stretches, the cycling unit's power draw falls with the load and the price difference comes back. Check the connection too, since sizes can differ by one step.

It can, provided the air reaching the dryer stays within that 200°F rating at full load on the hottest afternoon, because the successor carries its own cooling stage. Read the discharge temperature in midsummer before removing anything. A working aftercooler is still worth keeping: it drops bulk water before the receiver, eases the load on the drains, and leaves the higher rating as margin for a worn valve or a hot day rather than using it up.

The serial number on the nameplate dates the unit, and the refrigerant listed beside it is a second clue: R-134a or R-407C points to one of the retired lines. Age alone is no reason to replace a dryer that still holds it's dew point. One that has lost capacity, leaks refrigerant or has drifted out of its rating despite a clean condenser is the one to replace first.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales