Dental practices, laboratories and electronics benches run on small oil-free compressors of 1 to 5 hp delivering 5 to 30 SCFM, and the air goes into handpieces, analyzers and pick-and-place heads that tolerate neither water nor oil. The dryer is one of the 7 to 32 SCFM plug-in units, sized from the chairs or instruments on the line, with a particulate afterfilter instead of an oil-removal set.
An oil-free piston or scroll compressor has no oil to carry over, which removes the coalescer question, but it also has no oil to carry heat away, so a small oil-free head without an aftercooler can discharge air above 150°F. The dryer choice therefore rests on two numbers: the sum of what the chairs or instruments draw, and the temperature at the tank outlet.
Peak draw with every user on the line running at once. Dryer sizes at 100 psig and plant-temperature inlet; the second column applies the 0.65 inlet factor for an oil-free head with no aftercooler delivering 120°F air to the dryer.
| DUTY | PEAK AIR DRAW | DRYER SIZE, COOLED AIR | DRYER SIZE, 120°F INLET | DRYER BAND |
| Two-chair dental office | 4 to 6 SCFM | 7 SCFM | 10 to 11 SCFM | 5 to 50 SCFM |
| Five-chair practice | 8 to 12 SCFM | 11 to 15 SCFM | 15 to 20 SCFM | 5 to 50 SCFM |
| Ten-chair clinic | 16 to 24 SCFM | 25 SCFM | 32 to 42 SCFM | 5 to 50 SCFM |
| Dental lab with sandblaster | 15 to 20 SCFM | 20 to 25 SCFM | 30 to 32 SCFM | 5 to 50 SCFM |
| QC lab instrument air | 5 to 10 SCFM | 10 to 11 SCFM | 15 SCFM | 5 to 50 SCFM |
| Electronics assembly line | 20 to 30 SCFM | 30 to 32 SCFM | 42 to 50 SCFM | 5 to 50 SCFM |
The 7, 11 and 15 SCFM cabinet units and the 10 to 30 SCFM direct-expansion sizes are the dryers for this duty: 115 V, 3/8 or 1/2 in connections, 0.15 to 0.35 kW, and quiet enough for an equipment closet next to an operatory.
An oil-free piston compressor with no aftercooler and a short line to the dryer can deliver air well above 130°F. The 25 SCFM high-inlet-temperature dryers take 180 to 200°F air directly and give a 50°F dew point, which is adequate for handpieces and blast cabinets but not for instruments that call for class 4.
The compressor, tank and dryer usually share a closet or mechanical room, and the questions are noise, heat, drain water and keeping the air oil-free from head to handpiece.
Pipe the dryer after the tank with a 1 micron particulate filter ahead of it and a 0.01 micron filter behind; on an oil-free system the afterfilter is there for particles and any residual aerosol from the tank, not for compressor oil, and an activated carbon stage is only needed where the specification calls for oil vapor removal. Fit a zero-loss automatic drain on the tank and route the tank, filter and dryer drains to a sink or condensate neutralizer rather than a bucket, because a clinic cannot have water standing under equipment.
A dryer in this class draws under 0.4 kW and can sit on a wall bracket above the compressor, but its condenser needs air that has not already been warmed by the compressor, so leave a hand's width behind it and do not box it in with the tank. Where the practice or lab specifies a dew point below 38°F, a small desiccant dryer goes downstream of the refrigerated unit, which then does the bulk drying and protects the desiccant from liquid water.
A five-chair practice on a 3 hp oil-free duplex is the 11 or 15 SCFM dryer with the air cooled; connected straight to a hot tank it is the 20 SCFM standard size or the 25 SCFM high-inlet-temperature unit.
Size a dryer for my practice or lab
Hotter than most people expect. With no oil to carry heat out of the head and no aftercooler, a small oil-free unit can deliver air above 150°F, and a short line to the dryer barely cools it. Measure at the tank outlet with the compressor working its normal duty. At 120°F a standard dryer carries only 0.65 of its rating, which is why the hot column on this page runs a size or two larger.
Yes, provided the condenser gets air the compressor has not already heated. Mount it on a bracket with clear space behind it, never boxed in against the tank, and keep the closet ventilated; a sealed closet in summer turns every dryer in to a struggling one. Run its drain hose to the same sink or neutralizer as the tank drain so no water ever stands on the closet floor.
Most do not. Pick-and-place heads, actuators and test fixtures are content with a 38°F pressure dew point as long as the line stays indoors and warm. A desiccant stage goes in where the equipment specification calls for -40°F, or where the air feeds a moisture-sensitive analyzer. In that case keep the refrigerated unit ahead of it, so the desiccant bed never sees liquid water and lasts far longer.
Add the cabinet's draw to the handpieces that can run alongside it, because the blaster sets the peak the moment it is used. A lab that drew 8 to 12 SCFM for handpieces alone typically reaches 15 to 20 SCFM with a cabinet running, which moves the dryer to the 20 to 25 SCFM size. Check the compressor too, since it has to make that flow before any dryer can dry it.
Very little, but it has to happen. Clean the dust off the condenser fins every few months, because a clogged condenser is the most common reason a small dryer's dew point slips in summer. Change the particulate and 0.01 micron elements on the schedule printed on the housings, and confirm each automatic drain actually discharges; a stuck drain floods the separator and sends water to the handpieces.