An air-cooled refrigerated dryer moves heat from the compressed air into the room, and it can only do that when the room is cooler than its condenser. The rating assumes a 100°F room. At 110°F the refrigerant runs at a higher pressure and the dryer carries 88 percent of its nameplate; at 120°F it carries 75 percent, and a few degrees beyond that the high-pressure switch stops the compressor.
The ambient to use is the air temperature at the dryer's condenser intake on a summer afternoon, which in a compressor room is rarely the plant temperature and never the outdoor forecast.
The condenser is a finned coil with a fan blowing room air across it. Heat flows from the hot refrigerant to that air in proportion to the temperature difference between them, so as the room warms the refrigerant has to run hotter, its pressure rises, and the compressor delivers less cooling per kilowatt. Every air-cooled dryer therefore has two ambient numbers: the 100°F rating point, and a maximum of 110 to 122°F depending on the series, at which the unit still runs but at its derated capacity.
Divide the compressor's delivered flow by the ambient factor as well as the inlet and pressure factors. A 220 SCFM compressor in a 110°F room with 120°F inlet air is a 220 / (0.88 x 0.65), or 385 SCFM, duty.
The low end matters too. Below 34 to 45°F, depending on the series, the condensate inside the exchanger can freeze and the refrigerant pressure falls so low the circuit cannot regulate, so a dryer in an unheated shed or beside an open loading door in January needs the room heated or the dryer moved. Above the maximum ambient the choices are ventilation, relocation or a water-cooled unit.
Ventilation is nearly always the cheapest fix. A compressor room with an exhaust fan sized for the compressor's heat rejection and a louver low on the opposite wall runs within 10°F of outdoor air; without it the same room sits at 115°F, heated by the very machines trying to cool with it. Where the room cannot be cooled, the water-cooled builds of the FLXA, AES, VDR and HES Series carry an 85°F water rating that does not care what the room is doing.
The share of nameplate capacity an air-cooled dryer keeps in a room hotter than its 100°F rating point: 0.88 at 110°F and 0.75 at 120°F, applied by dividing the delivered flow by it.
The same compressor, two dryer sizes
A minimum, a rating point and a maximum
Room temperature, the inlet air it produces through a package aftercooler running 10°F above the room, and the rating-point duty at 100 psig.
| COMPRESSOR ROOM | AMBIENT FACTOR | INLET AIR | INLET FACTOR | DUTY FOR 220 SCFM | MODEL EXAMPLES |
| 100°F | 1.00 | 110°F | 0.80 | 275 SCFM | DXR 0325 NA, FLXA3.1-A |
| 110°F | 0.88 | 120°F | 0.65 | 385 SCFM | DXR 0400 NA, TMC 0400 N |
| 120°F | 0.75 | 130°F | 0.55 | 533 SCFM | DXR 0600 NA, FLXA5.5-A |
| Above 120°F | not rated | — | — | water-cooled dryer | FLXA8.1-W, AES-600W, VDR 2600 W |
| Below 34 to 45°F | not rated | — | — | heat the room or relocate | — |
Air the condenser draws, mid-afternoon in July
0.88 from 101 to 110°F, 0.75 from 111 to 120°F
Divide delivered flow by ambient, inlet and pressure
Confirm the room stays above the series minimum
Hang a thermometer at the height of the dryer's condenser intake, on the side the fan draws from, and read it at three in the afternoon in July. If the dryer is to go in a corner, behind the compressor or under a mezzanine, read it there, because the air the condenser draws is what matters and a compressor room can be 20°F warmer in one corner than another. Use 0.88 for anything from 101 to 110°F and 0.75 from 111 to 120°F; there is no credit for a room below 100°F, and no factor above 120°F because most series will not run there.
Give the condenser intake and discharge the clearance the installation drawing asks for, keep the discharge from blowing back into the intake, and never stand the dryer where the compressor's hot exhaust lands on it. A correctly sized dryer loses a frame size to nothing more than being parked in that exhaust stream.
Using the plant floor temperature for a dryer that lives in the compressor room. Sizing in spring. Forgetting that the compressor added last year raised the room by 10°F. Fitting the dryer outdoors under a roof and ignoring both the 120°F afternoons and the 20°F nights. Each ends the same way: a dryer that trips on high refrigerant pressure or passes water on the hottest, most humid days of the year.
A refrigerated dryer belongs indoors. Where it must sit in an unheated building, size for the summer maximum with the factors above and confirm the winter minimum stays above the series' lower limit, 34°F on the DXR Series and 41°F on the TMC Series. If it does not, a small heated enclosure costs less than the dryer it protects, and a drain that carries a heater, such as the heated model in the ND Series, keeps the condensate line from freezing shut.
Because the rating is built around 100°F and the published factors stop there. A cooler room does let the condenser run at a lower head pressure, and that shows up as margin on hot days rather than as a smaller dryer. Sizing below the rating on the strength of a mild room assumes it never warms, and a compressor room rarely stays mild once a second machine goes in beside the first.
That the condenser cannot shed heat fast enough and the refrigerant has reached the switch setting. Check the room at the condenser intake first; above the series maximum of 110 to 122°F, the cure is ventilation or relocation. If the room is within range, look at the fins, which clog with dust and oil mist, and at whether the discharge is blowing back into the intake. A trip that resets overnight is still a room or sizing problem.
On a 220 SCFM compressor, from a 385 SCFM duty down to 275 SCFM, one frame smaller. The fan lowers the room from 110 to 100°F and, because the aftercooler breathes that same air, takes the dryer inlet from 120 to 110°F as well, so two factors improve at once. Cooler air helps the compressor's own cooler too, which is why ventilation usually costs less than the dryer capacity it saves.
Not directly. An air-cooled condenser rejects heat by temperature difference, so its factor follows dry-bulb temperature alone. Humidity works through the compressor instead: on a humid day the aftercooler and receiver drop out more condensate and the drains work harder, but the air reaching the dryer is saturated either way, so its load is set by inlet temperature. Failures cluster on hot, humid afternoons because inlet temperature and room heat peak together.
Large enough for the heat the compressor rejects with the dryer's condenser load added on top, and paired with a louver low on the opposite wall for make-up air. The compressor data sheet gives its heat rejection; the dryer adds its refrigeration load plus its motor power. A properly ventilated room holds within about 10°F of outdoor air, while an undersized fan lets it settle near 115°F, which costs the dryer a frame size.
Often, and it is a sound fix where the compressor room cannot be ventilated. Keep the dryer after the receiver, size the connecting pipe to hold pressure drop down, and slope the wet run toward a drain. The dryer is then sized at the cooler room's ambient while the compressor stays put. Avoid a space that falls below 34 to 45°F in winter, depending on the series, or the problem simply moves to January.