Of the three corrections applied to a refrigerated dryer's rating, inlet air temperature is the one that moves a sizing furthest. The nameplate assumes 100°F air arriving at the dryer. Air at 110°F costs 20 percent of the rated capacity, 120°F costs 35 percent and 130°F costs 45 percent, because warmer air carries far more water and every pound of it has to be cooled to 38°F before that water lets go.
The number to find is the air temperature at the dryer inlet on the hottest afternoon of the year, and it is nearly always higher than the room.
Saturated compressed air at 100 psig holds nearly twice as much water vapor at 120°F as at 100°F, and all of it arrives at the dryer as heat load to be cooled and condensed. The refrigeration circuit has a fixed capacity, so when the load per cubic foot goes up, the cubic feet it can handle go down. The factors 0.80 at 110°F, 0.65 at 120°F and 0.55 at 130°F are the ratio between what the dryer carries at that inlet and what it carries at 100°F.
A 200 SCFM compressor whose air arrives at 120°F needs a dryer rated 200 divided by 0.65, or 308 SCFM, before the ambient and pressure factors are considered.
A rotary screw package with an air-cooled aftercooler discharges air 15 to 20°F above the air entering the aftercooler, and that air is the compressor room air, so a 95°F room delivers 110 to 115°F air. A dirty aftercooler adds 10°F more. A water-cooled aftercooler approaches its cooling water within 10 to 15°F, which is why it pays to check whether the tower water has crept up in summer.
A piston compressor with no aftercooler discharges 180 to 200°F air, which no standard refrigerated dryer is rated to accept. Either fit an aftercooler or choose one of the high inlet temperature dryers, which carry their own aftercooling stage and are rated at the hot inlet directly.
How far above its cooling air or water an aftercooler leaves the compressed air: 15 to 20°F on an air-cooled package, 10 to 15°F on a water-cooled one. A wider approach means a hotter dryer inlet.
The inlet reading that changes the model
Rating temperature and maximum temperature are different numbers
Capacity of a dryer rated 100 SCFM at each inlet temperature, and the rating-point duty an 88 SCFM compressor imposes, with ambient and pressure held at the rating point.
| INLET AIR | FACTOR | A 100 SCFM DRYER CARRIES | DUTY FOR 88 SCFM | MODEL EXAMPLES |
| 100°F | 1.00 | 100 SCFM | 88 SCFM | DXR 0105 NA, FLXA1.2-A |
| 110°F | 0.80 | 80 SCFM | 110 SCFM | DXR 0125 NA, TMC 0130 N |
| 120°F | 0.65 | 65 SCFM | 135 SCFM | DXR 0150 NA, FLXA1.5-A |
| 130°F | 0.55 | 55 SCFM | 160 SCFM | DXR 0185 NA, TMC 0170 N |
| 180 to 200°F, no aftercooler | not rated | — | high inlet temperature dryer | HTR 0100 (180°F), HRHT100A (200°F) |
A strap-on probe on the pipe after the receiver
Mid-afternoon in the hottest month, not in April
115°F takes 0.65, the lower of the two factors
Delivered SCFM over all factors, first model above
Put a thermometer well or a strap-on probe on the pipe at the dryer inlet, after the receiver, and read it mid-afternoon in the hottest month. If the reading falls between two factors, use the lower one; 115°F is sized at 0.65, not 0.80. Divide the compressor's delivered SCFM by that factor, apply the ambient and pressure factors from their own pages, and pick the first model at or above the result.
Every 10°F taken off the inlet is worth a frame size. Clean the aftercooler; a package aftercooler blocked with lint or oil mist is the commonest cause of 120°F air. Ventilate the compressor room so the aftercooler breathes outside air rather than its own discharge. Where the compressor has no aftercooler, adding one costs less than the larger dryer it would otherwise demand.
Taking the inlet reading in April. Reading the room thermostat instead of the pipe. Assuming a package aftercooler delivers 100°F air because the brochure said it could. Sizing for a piston compressor at 100°F when the air leaves the cylinder head at 190°F. Each produces a dryer that carries its load through the cool months and passes water from June to September.
Standard dryers here accept inlet air to 120°F on the HPRB and FLXA Series, 131°F on the smaller DXR sizes, 140°F on the larger DXR sizes and the TMC Series, and 158°F on the NXC and VDR Series, all derated by the factors above. Past that the HRHT Series takes 200°F air and the HTR Series takes 180°F, from 25 to 125 SCFM, with an aftercooling stage built in. They deliver a 50°F dew point, ISO 8573-1 class 6, which suits shop and service-bay air, and the 450°F GHTN filter goes ahead of them.
Compare the dryer inlet with the room. A healthy air-cooled package aftercooler delivers air 15 to 20°F above the air blowing through it; if the inlet reads 10°F beyond that, the core is likely fouled with lint or oil mist. Clean it and read again on a similar afternoon. A water-cooled aftercooler should run within 10 to 15°F of it's cooling water, so check the tower supply before blaming the exchanger.
Usually, where the compressor has none. Each 10°F taken off the inlet is worth about a frame size, and an aftercooler brings a piston's 180 to 200°F discharge down to a range a standard dryer will accept. It also drops out bulk condensate before the receiver, which eases the load on the drains. On a package screw that already has one, cleaning the core and ventilating the room come first.
Because the inlet carries the water. Saturated air at 100 psig holds nearly twice the vapor at 120°F that it holds at 100°F, and the refrigeration circuit has to cool that air and condense all of it, so a 120°F inlet costs 35 percent of capacity. A room at the same temperature works on the condenser instead and takes noticeably less. That gap is why the inlet reading, not the room thermometer, usually decides the frame size.
No. Each has a cooling stage built in ahead of its refrigeration circuit, so it takes the hot air as delivered: 180°F on one series and 200°F on the other, from 25 to 125 SCFM. The trade is a 50°F dew point, class 6, rather than 38°F. Where the duty needs class 4 air, a separate aftercooler feeding a standard dryer is the better arrangement; it costs more to install but delivers the lower dew point.
It nearly doubles it. At 130°F the factor is 0.55, so an 88 SCFM compressor needs a dryer rated about 160 SCFM before the room and pressure are counted. That is also close to the limit for several standard series, some of which accept only 120°F at the inlet, so check the data sheet maximum as well as the factor. Lowering the inlet with a clean aftercooler is usually the cheaper route.