1-805-484-2992

Quotes - Engineering - Sales

Condensate Drains for Refrigerated Dryers and Filters

Getting the water out of the dryer, filters and receiver

Request a quote

Condensate Drains for Refrigerated Dryers and Filters

A refrigerated dryer does nothing useful until the water it condenses leaves the system, and it leaves through a drain. So does the water knocked out by the aftercooler, the receiver, the separator and both filter bowls. Every one of those points needs its own drain, chosen for the volume it sees and the air it is allowed to waste, and every drain needs a discharge line that lets it open.

At the rating point a dryer condenses roughly 6 gallons a day for every 100 SCFM it dries, and the aftercooler and receiver ahead of it take out more than that again on a humid day. A drain that sticks shut floods the separator and sends all of it downstream.

Timed, zero-loss and float drains

A timed drain is a solenoid valve fired by a clock: an interval and an open time are set on the timer, and the valve opens whether there is water waiting or not. It is the cheapest drain, it tolerates dirty condensate, and it wastes compressed air on every cycle, which adds up on a receiver drain set for a wet August and left there through a dry January. The NETD, NPTD and NHPTD timed drains and the 530 Series electric drains cover 1/4 to 1/2 in outlets from 175 to 6,000 psig.

A zero-loss drain opens only when liquid is present. The electronic level-sensing types in the ND Series and the 600 Series demand drain use a capacitive sensor and a valve; the pneumatic types, the Snap-Trap and Trip-L-Trap and the magnetic float drains, use a float and need no power. None of them vents air, so they pay for themselves on any compressor that idles part of the day.

Drain series

Where each drain belongs

The receiver sees the largest volume and the dirtiest condensate, so it gets a heavy-duty drain: a 1/2 in timed 532 Series valve with its strainer, or a level-sensing ND Series drain sized for the compressor. The separator and the prefilter bowl see steady liquid and take a float drain or a Snap-Trap. The dryer's own separator is usually supplied with a zero-loss drain fitted, as on the DXR, TMC, FLXA, HRHT and HTR Series, or a timed electric drain on some larger units. The afterfilter bowl collects little and takes the smallest float drain.

Outdoors or in an unheated room, the heated model in the ND Series keeps the valve from freezing. On high-pressure systems the NHPTD drains to 6,000 psig and the 1,500 psig 532 Series valve are the choices.

Related installation pages

Zero-loss drainnoun

A condensate drain that opens only when liquid is present, sensed by a float or a capacitive level probe, so it discharges water without venting compressed air on every cycle.

ND Series Zero-Loss Drains zero loss condensate drain close-up

Worked example: drains for a 500 SCFM plant

Five collection points, five drains, one separator

  • Receiver: 532-04-300-1 timed drain with strainer, or a NED-LC level-sensing drain
  • GF 0700 WS separator and GFN 0700 M1 prefilter: float drains fitted to the housings
  • DXR 0500 NA dryer: zero-loss drain supplied on the unit
  • GFN 0700 M01 afterfilter: float drain; every line run separately to an oil-water separator
Snap-Trap & Trip-L-Trap Drains pneumatic zero loss drain close-up

Reading a drain specification

Five numbers that decide the fit

  • Maximum pressure: 175 to 300 psig on most drains, 1,500 to 6,000 psig on the high-pressure models
  • Inlet and outlet size: 1/4, 3/8 or 1/2 in
  • Power: 115 or 230 V for electric drains; none for pneumatic and magnetic float types
  • Discharge per cycle or capacity, and the body material: brass, aluminum or stainless

Drain selection by collection point

The condensate load at each point in a 100 psig system, the drain type that suits it and the series that supply it.

COLLECTION POINT CONDENSATE LOAD DRAIN TYPE SERIES
Aftercooler and receiver Largest; dirty, with compressor oil Timed 1/2 in valve with strainer, or level-sensing zero-loss 532 Series, ND Series NED-LC
Separator Steady bulk liquid Float drain fitted to the housing GF WS drain kit, Snap-Trap
Prefilter bowl Moderate; liquid and oil Float or pneumatic zero-loss Snap-Trap, ND Series NED 12
Dryer separator About 6 gallons a day per 100 SCFM at the rating point Zero-loss, usually supplied on the dryer As fitted; 600 Series demand drain as a replacement
Afterfilter bowl Small Smallest float drain Snap-Trap, filter housing drain
Outdoor or unheated Any of the above Heated zero-loss ND Series NHD 12
High pressure, 600 to 6,000 psig As the system High-pressure timed drain NHPTD, 532-02-1500
1

Count collection points

Receiver, separator, both filter bowls and the dryer itself

2

Match drain to load

Heavy-duty drain on the receiver, float drains on the bowls

3

Check pressure rating

175 to 300 psig on most; high-pressure models to 6,000 psig

4

Pipe each line alone

Short and sloped down, into an oil-water separator

Zero-loss, pneumatic and electric drains

ND Series Zero-Loss Drains zero loss condensate drain, three-quarter view

ND Series Zero-Loss Drains:

Condensate Drain

  • 290 psig max
  • 12 part numbers
Snap-Trap & Trip-L-Trap Drains pneumatic zero loss drain, three-quarter view

Snap-Trap & Trip-L-Trap Drains:

Condensate Drain

  • 175 psig max
  • 120°F max
  • 19 part numbers
530 & 600 Series Electric Drains electric condensate drain, three-quarter view

530 & 600 Series Electric Drains:

Condensate Drain

  • 1,500 psig max
  • 280°F max
  • 7 part numbers

Piping the discharge

Each drain gets its own line, short, sloped downward, and open at the far end into a vented collection point. Manifolding several drains into one pipe lets the pressure from one hold the others shut, and a long or rising line stalls a float drain. Keep the line at the drain's outlet size or larger and never fit a check valve or a trap it cannot lift against. Where the line runs outside, heat-trace it or use the heated drain.

Oil-water separation

Condensate from a lubricated compressor carries compressor oil, and most jurisdictions limit the oil in what goes to a sewer to a few parts per million. The drain lines therefore run to an oil-water separator, which lets the oil float off for collection and passes the water to the drain, rather than to a floor drain. The separator is sized on the total compressor horsepower it serves, and its own cartridge is a maintenence item.

Mistakes with drains

A timed drain set to its shortest interval and longest open time in July and never touched again, venting air all winter. A float drain on a receiver, where the volume and the sludge overwhelm it. Drains from three bowls piped into one 3/8 in line. A strainer never cleaned, so the valve seats on grit and leaks air continuously. And a dryer drain that discharges into a bucket nobody empties, which then backs up into the separator. Each shows up as water downstream or as an air leak the compressor is paying for.

Choosing between timed and zero-loss

Timed drains suit small, intermittent systems and dirty duty where their simplicity outweighs the air they waste. Zero-loss drains suit any plant that runs more than one shift or leaves the compressor up overnight, where the venting of a timed drain becomes a measurable share of the compressor's output. On the dryer itself the choice is normally already made, since most current series arrive with a zero-loss drain fitted, so the decision falls on the receiver and the filter bowls.

Picking and piping drains around the dryer

On two shifts the compressor stays loaded long enough that a timed valve venting on every cycle becomes a real running cost, so a level-sensing zero-loss drain usually wins at the receiver. A timed valve still earns its place where the condensate is heavy with sludge and someone cleans the strainer on a schedule. If you keep one there, reset its interval and open time each season rather than leaving the summer setting in all year.

Open it just long enough for the water to clear and a short burst of air to follow, then stretch the interval until the bowl or receiver never holds standing liquid between cycles. Check the setting again when the weather turns, because a humid day puts far more water into the receiver than a dry one. An open time that keeps creeping up over the months is usually a blocked strainer, not a wetter system.

Oil and fine scale build up around the float and its seat until the mechanism sticks. A discharge line that climbs or runs a long way makes it worse, because the drain then works against a standing column of water and sludge settles at the seat. The first sign is usually liquid in the prefilter bowl, then in the dryer separator. Pull the drain and clean it, and look hard at the line it empties into before blaming the drain itself.

Add up the horsepower of every lubricated compressor whose drains feed it, including the standby machine, because a standby still sheds condensate the moment it comes on line on a humid day. Choose the separator from its rating table on that total and budget for its cartridge, since a spent cartridge passes oil to the sewer as surely as having no separator at all. Bring each drain to the inlet on its own line.

Yes. Most drains are built for 175 to 300 psig, and one of those on a 600 psig line will leak or fail outright, so the high-pressure timed drains rated to 6,000 psig, or the 1,500 psig valve, take those positions. Pick the rating on the system's maximum pressure, relief setting included, not on the normal running pressure. Also make sure the collection point can take the flash, because high-pressure condensate leaves the valve far more violently than at 100 psig.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales