1-805-484-2992

Quotes - Engineering - Sales

Air Dryers for Pneumatic HVAC Controls

Instrument-quality air for pneumatic building controls

Request a quote

Air Dryers for Pneumatic HVAC Controls

A pneumatic building control system is the smallest compressed air plant in this section and the most sensitive to what is in the air. A duplex piston compressor of 1 to 5 hp in the mechanical room fills a tank to 80 to 100 psig; a pressure-reducing station drops it to 18 to 20 psig of main air; and that main air feeds thermostats, receiver-controllers, damper and valve actuators, relays and transducers all over the building through 1/4 in tube, each device metering its branch signal at 3 to 15 psig through a restrictor a few thousandths of an inch across. The whole system draws 5 to 20 SCFM.

Water in the main air condenses wherever the tube runs cold, in a ceiling plenum in winter or a shaft along an outside wall, and a drop of it in a thermostat's restrictor blocks the signal: the room overheats or freezes, a damper drifts open, a valve hunts. Oil aerosol from a lubricated compressor is worse because it never leaves; it gums restrictors and diaphragms one by one across the building. A refrigerated dryer with fine filtration ahead of the pressure-reducing valve is what stands between the compressor and a thousand small orifices.

Dry the air at tank pressure, ahead of the PRV, where the dryer works at the 80 to 100 psig it is rated for. A refrigerated dryer at a 38°F pressure dew point there becomes roughly a 12°F dew point once the pressure is reduced to 20 psig, which covers every run in a heated building. The flow is small, so the dryer is one of the smallest on the site: the HPRB Series at 7 to 25 SCFM or the DXR Series at 10 to 30 SCFM, wall-mounted beside the tank with a 1701 bypass valve so it can be isolated for service without dropping the main air.

The filter train matters as much as the dryer: a 1 micron prefilter, the dryer, a 0.01 micron coalescing filter and an activated carbon filter for oil vapor, all sized for the compressor and each with a drain. A control compressor cycles a third of the time and runs cool through its tank, so a standard dryer is fine; the non-cycling type draws about 0.2 kW, and at this flow no cycling dryer can pay back. The one case that moves the answer is main air that runs outdoors or through an unheated space in winter, where a class 2 desiccant stage downstream of the refrigerated unit is needed on that branch.

Request a control-air dryer quote
HPRB Series refrigerated air dryer
12°F

Main-air dew point after the PRV at 20 psigDrying at 100 psig and then letting the air down to 20 psig takes a 38°F pressure dew point to about 12°F, which keeps water out of any heated-building ceiling.

HPRB Series refrigerated air dryer detail

What wet or oily air does to pneumatic controls

The service calls that trace back to the compressor room

  • Thermostat restrictors blocked by a drop of condensate, rooms drifting hot or cold
  • Damper and valve actuators hunting or stuck as water collects in the branch line
  • Diaphragms and relays gummed by oil aerosol, replaced one by one across the building
  • Rusted main air tube and PRV internals after a winter of wet air in a cold plenum
DXR Series refrigerated air dryer

The control-air specification

What the mechanical room needs

  • Refrigerated dryer ahead of the PRV at tank pressure: 38°F pressure dew point, about 12°F at 20 psig main air
  • 1 micron prefilter, 0.01 micron coalescer and activated carbon filter, sized for the compressor with a drain on each
  • Wall-mounted 7 to 30 SCFM dryer with a 1701 bypass valve for service
  • Desiccant stage on any branch that crosses unheated space; an oil-free compressor at replacement

Dryers and filters that fit a control-air system

Ratings at 100 psig and 100°F inlet. A 2 to 5 hp control compressor delivers 7 to 18 SCFM, so the 7 to 25 SCFM dryers cover it; the HTR Series takes 180°F air where a dryer is close-coupled to a compressor without a tank.

SERIES TYPE FLOW RANGE MAX INLET MAX PRESSURE
HPRB Series Non-Cycling 7 to 50 SCFM 120°F 200 psig
DXR Series Non-Cycling 10 to 4,200 SCFM 131°F 203 psig
HTR Series High Inlet Temperature 25 to 125 SCFM 180°F 232 psig
GFN Series Filters Compressed Air Filter 6 to 1,500 SCFM — 232 psig
NGF Series Filters Compressed Air Filter 20 to 1,500 SCFM — 250 psig
1701 Bypass Valves & Mounting Brackets Bypass & Mounting 5 to 35 SCFM — 200 psig
Snap-Trap & Trip-L-Trap Drains Condensate Drain Call for sizing — 175 psig
PDM Dew Point Monitor Dew Point Monitor Call for sizing — 145 psig

Before signing off a control-air retrofit, confirm this.

  • Dryer at tank pressure, upstream of the pressure-reducing valve
  • Prefilter, coalescer and carbon stage each fitted with a drain
  • Bypass closed and dryer alarm wired to the automation system

Converting to DDC does not retire the compressor

Many buildings that converted their controls to direct digital control kept pneumatic actuators on the dampers and valves, driven by electronic-to-pneumatic transducers, because replacing every actuator was the expensive part of the job. The compressor, the dryer and the filters still serve those actuators, and the transducers are as sensitive to oil and water as the thermostats they replaced. A DDC front end also makes the dryer's alarm contact useful: wire it and the dew point monitor's relay into the automation system and the mechanical room reports a wet dryer before the first actuator sticks. When the control compressor is finally replaced, an oil-free unit with a tank, a small dryer and a two-stage filter train is the whole specification.

  • Keep the dryer and filters in service for pneumatic actuators after a DDC conversion
  • Wire the dryer alarm and the dew point monitor relay into the building automation system
  • Specify an oil-free compressor at replacement so the carbon filter can be dropped
HTR Series refrigerated air dryer

Where the dryer goes: before the PRV

Compressor, tank, 1 micron prefilter, dryer, 0.01 micron coalescer, carbon filter, then the pressure-reducing station and the main air. Drying at tank pressure does two things: the dryer works at the pressure it is rated for, and the dew point falls with the pressure when the PRV lets the air down. A 38°F pressure dew point at 100 psig is about 12°F at 20 psig, below any ceiling plenum in a heated building. Put the dryer after the PRV and it works at 20 psig, where its capacity is a fraction of its rating, and the 38°F it delivers is at main-air pressure, which is not enough in a cold plenum.

Sizing the smallest dryer on the site

A 3 hp control compressor delivers about 10 to 12 SCFM and a 5 hp unit about 18, so the 15 or 25 SCFM dryer covers nearly every building, and the 2 to 5 hp reciprocating page matches the sizes. Size to the compressor's delivery rather than the system's average draw, because the dryer sees full compressor flow whenever the tank is being filled.

Oil, filters and oil-free compressors

Pneumatic controls tolerate less oil than almost any other application, since a restrictor orifice a few thousandths accross gums shut on a film a machine tool would never notice. On a lubricated compressor the 0.01 micron coalescing filter behind the dryer stops the aerosol and the activated carbon filter behind it stops the vapor; the carbon element is changed on hours, since a saturated bed shows no pressure drop. An oil-free compressor removes the source and leaves only the particle filters to maintain. The filter placement page sets out the order.

Main air in unheated spaces

Main air that runs to a rooftop unit or through an unconditioned attic sees temperatures below any refrigerated dew point in winter, and water condenses in the tube and freezes at the actuator. The refrigerated dryer still does the bulk of the work; a small desiccant cartridge or membrane dryer downstream on that branch takes the dew point to class 2 for the part of the system that needs it. The refrigerated versus desiccant page explains where the line falls.

Drying air for pneumatic building controls

Figure about 10 to 12 SCFM from a 3 hp duplex and about 18 from a 5 hp, and the 15 or 25 SCFM dryer then covers nearly any building. Size from the compressor's delivery, not from the trickle the thermostats bleed, because the dryer sees full compressor flow every time the tank refills. A unit picked for the average draw floods during each fill and passes water into the main air, which shows up weeks later as drifting setpoints.

It saves nothing and costs dew point. At 20 psig a dryer rated at 100 psig carries only a small fraction of its nameplate flow, so a much larger unit would be needed for the same compressor. Worse, its 38°F would then be a dew point at main-air pressure rather than tank pressure, which leaves no margin in a cold plenum or a shaft along an outside wall. Mount it at the tank, upstream of the PRV, and let the pressure reduction lower the dew point for you.

The building runs on wet, unfiltered air, and nobody notices for weeks. The bypass routes compressor air around the dryer, so system pressure holds and nothing alarms, yet every tank fill pushes saturated air into the main. The first signs are a few rooms drifting off setpoint in the coldest part of the building. Make closing the bypass the last step of every service visit, and read the dryer outlet dew point before leaving the mechanical room.

Wire it, along with the dew point monitor's relay if one is fitted. A refrigerated dryer that loses its charge or trips in a hot mechanical room keeps passing air, only wet, and without the contact the first evidence is a comfort complaint from an occupied floor. With the alarm on the building automation system the operator sees the fault the same hour and can start the repair before condensate reaches the main air tube. The cost is a pair of conductors.

More than its size suggests. The tank, the prefilter, the dryer separator and the coalescer each collect liquid, and in a mechanical room nobody visits daily a manual valve gets opened when someone remembers. Once one bowl fills, its water carries through to the next stage and on into the main air. Fit an automatic drain at each point, such as the small pneumatic float traps made for this duty, and test every one at the annual service.

Usually yes, at the point the old machine needs a rebuild. Oil aerosol is the contaminant pneumatic controls handle worst, because a trace too thin to notice on a shop tool is enough to close the tiny restrictor in a thermostat or relay. An oil-free compressor removes the source, so the activated carbon stage and its scheduled element changes can go. Keep the prefilter, the dryer and the coalescer, since ring wear particles and mechanical room dust still need catching.

More on control-air drying

Small duplex piston compressor with a refrigerated dryer in a mechanical room

Dryers for 2 to 5 hp reciprocating compressors

The control-air compressor class, matched to the 7 to 25 SCFM dryers that fit it.

Learn More
Woodworking

Woodworking

A screw compressor with its own aftercooler feeds a standard dryer directly.

Learn More
Textiles

Textiles

A weaving mill is one of the largest compressed air users in any industry.

Learn More

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales