1-805-484-2992

Quotes - Engineering - Sales

Refrigerated Air Dryers for CNC & Machining

Dry air for spindle purge, tool changers and chip blast

Request a quote

Refrigerated Air Dryers for CNC & Machining

A machining center uses compressed air in four places that all hate water: the spindle air purge and air-oil bearing lubrication, the tool changer and chuck cylinders, the air blast that clears chips off the part, and the probe and gauge lines. Water in any of them shows up as a rusted spindle taper, a sticking drawbar, chips welded to a wet part face or a probe that drifts.

A refrigerated dryer holding a 38°F pressure dew point takes the shop air below the temperature of any surface it will touch, so nothing condenses inside the machine. For a machine shop that is the whole requirement; the desiccant class of dryer is only needed where the line runs outdoors or the air feeds a laser.

Sizing follows the compressor, not the machine: a 25 hp rotary screw feeding six machining centers is a 110 to 125 SCFM dryer duty, and the dryer goes at the compressor room, after the receiver, so the whole shop gets dry air. Point-of-use dryers only make sense for one machine on a long run from a wet header.

Machine shops run two shifts with the compressor loaded most of the time, which is the case where a non-cycling dryer costs nothing extra to run. A cycling dryer earns its premium when the shop idles nights and weekends with the compressor still up.

Request a machine-shop dryer quote
HPRB Series refrigerated air dryer
105°F

pipe reading that points at the aftercoolerAir from a working aftercooler arrives close to the dryer's rating; well above this figure, cleaning the cooler costs far less than buying a larger dryer.

HPRB Series refrigerated air dryer detail

What water does inside a machine tool

The failures a wet air line causes, and how long they take

  • Spindle taper and drawbar corrosion within a season of wet purge air
  • Tool changer cylinders sticking as water washes the lubricant out
  • Air blast leaving a film that ruins a surface finish or a coating step
  • Probe and gauge readings drifting as condensate collects in the lines
DXR Series refrigerated air dryer

The dryer specification for a machine shop

What to ask for and what to skip

  • 38°F pressure dew point, ISO 8573-1 class 4; class 3 desiccant only for laser or outdoor lines
  • Dryer sized to the compressor's full output at the room temperature of the compressor area
  • A 1 micron prefilter ahead of the dryer and a 0.01 micron oil-removal filter behind it
  • A zero-loss drain so the dryer does not bleed air every 30 seconds through a timer

Dryers that fit a machine shop

Flow ranges at 100 psig and 100°F inlet. A 15 to 50 hp screw compressor lands in the 65 to 250 SCFM band; larger shops with a 60 to 150 hp compressor use the 300 to 700 SCFM sizes.

SERIES TYPE FLOW RANGE MAX INLET MAX PRESSURE
HPRB Series Non-Cycling 7 to 50 SCFM 120°F 200 psig
DXR Series Non-Cycling 10 to 4,200 SCFM 131°F 203 psig
FLXA Series Cycling 75 to 2,000 SCFM 120°F —
TMC Series Thermal Mass Cycling 30 to 635 SCFM 140°F 210 psig
NXC Series Cycling 20 to 2,000 SCFM 158°F 232 psig
GFN Series Filters Compressed Air Filter 6 to 1,500 SCFM — 232 psig
NGF Series Filters Compressed Air Filter 20 to 1,500 SCFM — 250 psig
ND Series Zero-Loss Drains Condensate Drain Call for sizing — 290 psig

A machine shop dryer install should look like this.

  • Receiver ahead of the dryer, never the compressor discharge directly
  • Size taken from nameplate delivery and summer room temperature
  • Zero-loss drain in place of a timer that bleeds every 30 seconds

The dryer is only as good as the aftercooler in front of it

Every refrigerated dryer is rated with 100°F air arriving at its inlet. A rotary screw compressor with a working aftercooler delivers air 15 to 20°F above the room, which on a hot day is right at the rating point. A compressor whose aftercooler is plugged with dust delivers 140°F air and the dryer loses close to half its capacity without anyone changing a setting.

Before sizing up a dryer that seems to be failing on hot days, put a thermometer on the pipe between compressor and dryer. If it reads more than about 105°F the answer is usually a cleaned or added aftercooler, not a bigger dryer.

  • Measure inlet temperature on the hottest afternoon of the year
  • Clean the compressor aftercooler before resizing the dryer
  • Keep the pipe between compressor and dryer short and uninsulated
FLXA Series refrigerated air dryer

Where the dryer goes

Compressor, aftercooler, receiver, prefilter, dryer, afterfilter, then the header. The receiver ahead of the dryer smooths the flow and drops out the bulk of the water, which is why the dryer should never be piped straight off the compressor discharge. In a shop that grew one compressor at a time, put the dryer downstream of the point where all the compressors join, sized for their combined output, or run one dryer per compressor if they are in different rooms.

Sizing the dryer for a machine shop

Take the compressor nameplate delivery, not the horsepower guess, and check the compressor room temperature on a summer afternoon. A dryer rated at 100°F ambient loses about 20 percent of its capacity at 110°F. A 25 hp screw delivering 106 SCFM in a 105°F compressor room wants the 125 or 150 SCFM dryer, not the 105. The ambient correction page gives the factors.

Cycling or non-cycling for a machine shop

A two-shift shop with the compressor loaded 70 percent of the time gets almost nothing back from a cycling dryer; the non-cycling unit is cheaper to buy and simpler to keep. A job shop that runs days only, with the compressor idling overnight to hold pressure for the CMM room, saves real power with a cycling dryer because the refrigeration compressor stops while the thermal mass carries the small night load. Run the numbers both ways on the cycling versus non-cycling page.

Filtration for machine tools

Machining centers with air-oil spindle lubrication need clean air more than most: the 0.01 micron oil-removal filter behind the dryer keeps compressor oil out of the spindle bearings, where it would mix with the metered lubricant and change its viscosity. Put the prefilter before the dryer where the air is cool and the water has dropped out, and change elements on pressure drop, not the calendar.

Keeping water out of the machine tool

At every change of season, and any time the dryer starts losing its dew point on warm afternoons. Machine shop air carries coolant mist and fine chips, and both stick to aftercooler fins until the compressor is delivering air far hotter than the dryer is rated for. A surface thermometer on the pipe between compressor and dryer tells the story in a minute; a reading well above 105°F means clean the cooler before touching the dryer.

Yes, through its condenser. An air-cooled dryer pulls room air across the coil, and oily mist plus fine swarf builds a film on the fins that insulates them, so the dryer rejects less heat and behaves as if the room were hotter. Keep the dryer in the compressor room, away from the machining floor, and clean the coil when the fins look dull. A mist collector on the worst machines helps the compressor intake too.

Clean, dry and steady. Air bearings float the axes on a film a few microns thick, so water, oil and particles all damage the bearing faces and the measurement with them. A 38°F dryer works in a temperature-controlled CMM room, but the air also needs a 0.01 micron coalescer and usually a fine particulate stage at the machine. Hold pressure with a precision regulator, because bearing stiffness, and so the reading, shifts with supply pressure.

Because the blast is laying condensate and compressor oil on the part while it clears the chips. On a part going straight to inspection that is a cosmetic mark; on one going to anodizing, paint or bonding, it is a reject. A dried supply removes the water, and the 0.01 micron oil-removal filter behind the dryer removes the oil film. If spots remain, check whether the blast nozzle is fed from a drop off the bottom of the header.

It removes the cause, not the damage. Wet purge and unclamp air corrode the drawbar, the gripper fingers and the spindle taper, and once pitted they keep sticking untill the spindle is serviced. Install the dryer first, so rebuilt parts are not ruined the same way, then have the drawbar and taper inspected. A machine that still drops tools or throws a clamp alarm after that usually has a tired spring pack rather than an air problem.

It does, if the shop cannot stop for an element change. A three-valve bypass lets the dryer and its filters be isolated while air flows around them, and on a small dryer a single-body bypass valve does the same job in one fitting. The risk is the open bypass nobody closes, which sends wet air into the machines for weeks before anyone notices. Tag the valve, and check the outlet dew point after every service.

More on drying shop air

Rotary screw compressor in a machine shop compressor room

Dryers for 15 to 50 hp rotary screw compressors

The compressor sizes most machine shops run, matched to the dryer band that fits them.

Learn More
Pneumatic Tools & Controls

Pneumatic Tools & Controls

Sizing starts with the compressor, not the tool count, because tools are intermittent and the compressor is what the dryer actually sees.

Learn More
Laser & Plasma Cutting

Laser & Plasma Cutting

Compressed air for plasma tables and fiber laser assist gas: where a refrigerated dryer is enough and where a desiccant stage is required.

Learn More

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales