1-805-484-2992

Quotes - Engineering - Sales

Dew Point and ISO 8573-1 Air Quality Classes

Reading the three ISO 8573-1 numbers: particles, water, oil

Request a quote

Dew Point and ISO 8573-1 Air Quality Classes

ISO 8573-1:2010 describes compressed air purity with three numbers in a fixed order: particles, water and oil. A specification of 2:4:2 means class 2 particles, class 4 water and class 2 oil. The water class is a pressure dew point, the temperature at which water condenses out of the air at line pressure, and a refrigerated dryer at its 38°F rating meets class 4. The particle and oil classes are met by the filters around the dryer, not by the dryer itself.

Most purity problems on plant air are specification problems: a class written stricter than the process needs, or a dew point quoted at atmospheric pressure when the dryer is rated at line pressure.

Pressure dew point against atmospheric dew point

Dew point depends on pressure. Air at a 38°F pressure dew point at 100 psig, let down to atmosphere, has a dew point of roughly minus 5°F, because the water vapor is spread through seven times the volume; a minus 40°F pressure dew point corresponds to roughly minus 70°F atmospheric. Every dryer on this site and every ISO 8573-1 water class is a pressure dew point, so a requirement written as an atmospheric dew point must be converted before it is compared with either.

The practical test is simpler than the conversion: water condenses in a line only where the pipe is colder than the pressure dew point of the air in it. At 38°F that means nowhere inside a heated building.

Dew point in practice

Particles and oil: the filters set those classes

Particle classes count solids per cubic meter in three size ranges, and oil classes limit total oil, aerosol plus vapor, in milligrams per cubic meter: class 1 is 0.01 mg or less, class 2 is 0.1, class 3 is 1 and class 4 is 5. A 1 micron prefilter such as the GFN M1 grade takes oil to class 3, a 0.01 micron coalescing afterfilter such as the GFN M01 grade takes it to class 2, and an activated carbon stage after the coalescer takes the remaining vapor to class 1.

The same 0.01 micron afterfilter normally delivers class 1 or 2 particles, provided it sits after the dryer where the air is coldest and the aerosols are easiest to catch. The filter placement page sets out the order.

Filters by class

Pressure dew pointnoun

The temperature at which water starts to condense from compressed air at its own line pressure. Dryer ratings and ISO 8573-1 water classes use it, and it reads far warmer than the same air's atmospheric dew point.

PDM Dew Point Monitor dew point monitor close-up

Worked example: a CNC cell specified 2:4:2

Turning a purity class into equipment

  • Class 4 water: a refrigerated dryer at its 38°F rating, sized on the corrected duty
  • Class 2 oil: a 0.01 micron coalescing afterfilter after the dryer, with a 1 micron prefilter ahead of it
  • Class 2 particles: met by the same 0.01 micron afterfilter
  • Had the spec read 2:4:1, an activated carbon filter would follow the coalescer
HF Series Filters compressed air filter close-up

Reading a purity specification

Three digits, always in the same order

  • First digit particles, second water, third oil: 1:4:1 is not the same air as 4:1:1
  • A water class is a pressure dew point; convert any atmospheric figure first
  • Class 0 is not zero: it is a limit the buyer writes, stricter than class 1
  • A dash or X means no limit is placed on that contaminant

ISO 8573-1:2010 purity classes

Water as pressure dew point, particles as the count in the 1 to 5 micron range per cubic meter, and oil as total aerosol, liquid and vapor. Classes 1 to 5 particles also carry limits in the smaller size ranges.

CLASS WATER, PRESSURE DEW POINT PARTICLES, 1 TO 5 MICRON PER m3 OIL, mg PER m3 HOW IT IS MET
1 Minus 94°F (minus 70°C) or lower 10 or fewer 0.01 or less Desiccant dryer; 0.01 micron coalescer plus activated carbon
2 Minus 40°F or lower 100 or fewer 0.1 or less Desiccant dryer; 0.01 micron coalescer
3 Minus 4°F (minus 20°C) or lower 1,000 or fewer 1 or less Desiccant dryer; 1 micron filter
4 37.4°F (3°C) or lower 10,000 or fewer 5 or less Refrigerated dryer at its 38°F rating; separator and 1 micron filter
5 44.6°F (7°C) or lower 100,000 or fewer No class (X above 5) Refrigerated dryer; cycling models rated 41°F
6 50°F (10°C) or lower By mass, 5 mg per m3 or less — High inlet temperature dryers, HRHT and HTR Series
1

Find the strictest use

Write the class for the driest point, not the plant

2

Set the water digit

Class 4 is refrigerated at 38°F; class 2 or 3 is desiccant

3

Choose the filters

1 micron before, 0.01 micron after, carbon for class 1 oil

4

Verify at the outlet

Read pressure dew point at the dryer outlet

Instruments and filters that set the class

PDM Dew Point Monitor dew point monitor, three-quarter view

PDM Dew Point Monitor:

Dew Point Monitor

  • 145 psig max
  • 122°F max
  • 1 part numbers
HF Series Filters compressed air filter, three-quarter view

HF Series Filters:

Compressed Air Filter

  • 20 to 21,250 SCFM
  • 300 psig max
  • 150°F max
GFN Series Filters compressed air filter, three-quarter view

GFN Series Filters:

Compressed Air Filter

  • 6 to 1,500 SCFM
  • 232 psig max
  • 176°F max

Writing a class the system can meet

Start from the driest, cleanest point of use and write the class for that, not for the whole plant. Class 4 water covers every indoor duty; class 2 or 3 is a desiccant dryer. Class 2 oil is the normal target for tools, machines and paint, and class 1 is for food contact, pharmaceutical and electronics duties where vapor matters. Class 2 particles follows from the afterfilter. A body shop written as 1:2:1 has specified a desiccant dryer and three filters where a refrigerated dryer and two filters would do.

Verifying it

A dew point instrument at the dryer outlet is the only proof of the water class. The PDM monitor samples through a quick-connect fitting, reads pressure dew point from plus 68 down to minus 148°F, and can be carried between dryers or wall-mounted with its alarm contacts wired to a PLC. Oil and particle classes are verified by sampling to the ISO 8573 test methods where a written class has to be certified.

Mistakes in specification

Quoting an atmospheric dew point as if it were a pressure dew point, which makes a 38°F dryer look like it fails a spec it comfortably meets. Reading the class digits in the wrong order. Expecting the dryer to deliver an oil class, when oil removal is entirely the filters' work. Asking for class 0 without writing its limit. Specifying a lower water class than the process needs, which buys a desiccant dryer and its purge air for nothing.

What a refrigerated system delivers

A refrigerated dryer at its rating with a 1 micron prefilter and a 0.01 micron afterfilter delivers class 4 water and class 2 oil, with particles at class 1 or 2, which the standard would write as 2:4:2 or better. The high inlet temperature dryers deliver class 6 water at 50°F, and a few cycling models are rated class 5 at 41°F. Adding an activated carbon stage after the afterfilter moves the oil to class 1 for food and pharmaceutical duties. Anything below class 4 water comes from a desiccant dryer, and we say so and help source it.

Writing a purity class the air can meet

As written, yes, because class 2 water is a minus 40°F pressure dew point and no refrigerated dryer reaches it. The real question is whether the process asked for it on purpose. A body shop or a machining cell handed 1:2:1 is usually carrying a borrowed specification, and 2:4:2 air from a refrigerated dryer and two filters serves it without the purge air a desiccant unit vents. Rewrite the class from the driest point of use.

It gets drier. Letting the pressure down spreads the same water vapor through a larger volume, so the dew point at the lower pressure falls below 38°F, and at atmosphere it reaches roughly minus 5°F. That is why nothing condenses at the regulator or the tool. It also makes the dryer outlet, at full line pressure, the hardest place to meet class 4 and the right place to measure it; a reading taken downstream of a regulator flatters the system.

Cold air is where the oil has condensed into an aerosol that a coalescing element can catch, and the same element takes out the fine particles. Mounted ahead of the dryer, a 0.01 micron filter sees warm air carrying much of its oil as vapor, lets it pass, and that vapor then condenses downstream where nothing stops it. The result is a filter with a clean differential and an oily header.

Class 3, which allows 1 mg of oil per cubic meter. That falls short of the class 2 that tools, machines and paint normally need, and well short of food contact work. The prefilter's real job is protecting the dryer's exchanger from liquid oil and dirt. The class the plant receives is set by the 0.01 micron coalescer after the dryer, and by a carbon stage after that where class 1 is written.

Only on paper, in most plants. Class 5 allows a pressure dew point up to 44.6°F, and the cycling models rated there sit at 41°F, a few degrees above a standard unit; inside a heated building that margin goes unnoticed. A written specification that calls for class 4, though, is not met by a class 5 rating, so match the dryer's rated class to the document as well as to the plant.

By sampling the air to the ISO 8573 test methods, which is laboratory work rather than a gauge reading. A dew point instrument proves the water class on site, but oil and particle classes need a sample drawn and analyzed under the procedure the standard sets. Take it after the final filter with the system at normal load, because a lightly loaded line gives a result the plant will not see at full production.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales